Clearance Index Enquire

Compare

Busbar insulation tape against heat-shrink sleeve

A sleeve is a continuous tube and has to pass over a free bar end. Tape does not. On a panel already bolted and torqued that settles the job, before any wall grade or the 320-to-140 mm clearance argument is opened.

Start with whether the joint comes apart

A busbar sleeve is a continuous tube, cut from a reel and recovered onto the bar at a shrink temperature of 125 °C. It is entered from an open end, so either the bar is threaded before the joint is made or the joint is opened to thread it. Tape is wound onto the bar where it lies and asks for working access and nothing else.

On a panel still on the bench the bars are loose and threading costs nothing. On a panel that is wired, torqued and tested, a sleeve means opening a joint that has already been signed off. Neither material changed between those two cases; the assembly state did.

The second split is where the finished wall comes from. The chart fixes it: GSC walls run 0.69 to 1.50 mm, GMB 1.70 to 3.30 mm and GHB 3.20 to 4.20 mm, each to ±10%, so GMB 100/38 puts 3.00 mm of cross-linked polyolefin on any rectangular bar summing 83 to 126 mm across width and breadth. A wrapped wall is tape thickness times turn count times overlap, and all three are settled at the bar by whoever is holding the roll.

That matters because the published clearance reductions are stated against named wall grades. The manufacturer's table sets a medium-wall and a heavy-wall column beside the uninsulated IEC 71-2 figure — at 36 kV, 140 mm phase to phase on heavy wall against 320 mm bare on rectangular bar. It carries no column for a wrap, so a taped bar has no clearance figure to quote.

Length is the third split and it shows up only at the top of the range. The reel-length column falls from 100 m on GSC 16/8 to 25 m through most of the GMB and GHB series, then to 1.5 m on GMB 205/85, GMB 250/100, GHB 205/85 and GHB 250/120. A long run in a 250 mm-class section therefore arrives in 1.5 m pieces, and the covering itself has joints in it.

Four coverings, six questions

Tape, sleeve, shroud and sheet are not four answers to one question.

QuestionWrapped tapeHeat-shrink sleeveMoulded shroudBus sheet
Needs a free bar endNoYesNoNo
Covers a tee or an elbowNoNoYes, moulded to the shapeYes, cut to the joint
Finished wall is set bythe fitter's turns and overlapthe chart — GMB 100/38 is 3.00 mm ±10%the mould — PVC 2.00 mm at 12 kV, 4.50 mm at 38 kVthe sheet — GHHS 4 mm, 5.5 mm with its adhesive
Published as removable and re-usableNot publishedNo, it is shrunk onto the barYes, in minutesNo, it is adhesive-lined and shrunk
Installed withNot publishedHeat, to a 125 °C shrink temperatureFasteners, supplied with itA gas torch or a hot air gun
Voltage in the manufacturer's dataNot published in these sourcesTo 36 kVTo 36 kVGMHS to 17.5 kV, GHHS to 36 kV

When tape is the right call

Each of these is a case where the sleeve is unavailable, not a case where a wrap is the better covering.

  • The panel is already bolted up. Threading a sleeve means opening a joint that is already made and already tested.
  • The bar has no free end. A run landing on fixed supports at both ends cannot be withdrawn, and a tube has nowhere to start.
  • The bar cannot be released for long. That constraint is the reader's own: no installation time is published for either covering, here or in the manufacturer's data.
  • A local repair. Where a short length of existing covering is damaged, cutting a whole sleeve off the run is out of proportion to the defect.
  • The section is past the chart. The largest rectangular entry published is 314 mm of width plus breadth, on GMB 250/100 and GHB 250/120. Above that there is no size code to read off.

What a wrap gives up

Five of these come out of the published data. The sixth is a working judgement and is marked as one.

  • Repeatability. Two fitters produce two walls on identical bars. The chart does not vary that way: GSC 0.69 to 1.50 mm rated to 3.3 kV, GMB 1.70 to 3.30 mm to 24 kV, GHB 3.20 to 4.20 mm to 36 kV, each ±10% and each printed against its size code.
  • The clearance argument. Panel width is the commercial reason to insulate a bar at all, and the reduction is published against a named wall grade. A wrap forfeits it.
  • Tees and elbows. The manufacturer's bus sheet page places tees, elbows and irregular connections where neither tubing nor tape can be used — that routing is theirs, not an inference drawn here.
  • A published overlap figure. The sheet has one: extend a minimum 100 mm onto each leg of the joint before shrinking, and overlap existing insulation by 65 mm after. Nothing equivalent is published for a wrap, and overlap is exactly what sets a wrapped wall.
  • Re-usability. It is published for two parts only — BUSBOOT and BUSCAP, both of which install, remove and replace in minutes. It is published for neither the sleeve, the sheet nor a tape.
  • Judgement, not a measurement: a shrunk sleeve either conformed to the bar or visibly did not, and an inspector can see which. A wrapped wall can only be checked by measuring it, and a missed lap sits under the next turn.

No tape specification is printed on this page

No dimensional table for a busbar tape exists in this site's sources, so none appears here and none has been reconstructed from the sleeve data. The manufacturer's switchgear insulation index confirms that a Bustape heat-shrink tape and a non-shrinkable high-voltage tape are made; the dimensions sit with the tape datasheet at heatshrink-sleeve.com/heat-shrink-tape/. One page further is a better answer than a wall thickness invented to fill a column.

Questions this comparison raises

Can a sleeve be fitted without opening the joint?
No. The tube is continuous and has to pass over an open end, so either the joint is dismantled or the bar is withdrawn. Where neither is possible the covering is tape, a shroud that fits over the made joint, or a sheet cut to it.
Is busbar tape rated to the same voltage as a sleeve?
That cannot be answered from the data behind this site, which publishes no voltage rating for a tape. The sleeve side is explicit: the range meets ANSI C37.20.2 for medium-voltage switchgear application to 36 kV, split into Thin Wall to 3.3 kV, Medium Wall to 24 kV and Heavy Wall to 36 kV.
Does wrapping a bar let the panel be made narrower?
The reductions in the manufacturer's table belong to a named wall grade, so they do not transfer to a wrap. Heavy wall on rectangular bar at 36 kV is listed at 140 mm phase to phase against 320 mm uninsulated; a taped bar has no equivalent row. Work panel width through on the clearance page.
What covers a tee if neither tape nor a tube will?
A moulded shroud or a cut sheet. GHHS ships as a 1200 × 430 mm sheet, 4 mm thick and 5.5 mm including its 1.5 mm adhesive layer; a 100 mm busbar tee takes a 450 × 325 mm cut, three to the sheet. The connections guide maps the rest of the joint geometries onto parts.
Which of the four is published as removable?
The shroud, and the end cap at a bar end. BUSBOOT installs, removes and replaces in minutes and is supplied complete with its fasteners; BUSCAP, in sizes GBC1 to GBC18, does the same over a live bar end. The sleeve and the sheet are shrunk on, and a shrunk part comes off by being cut.

What this page does not establish

This sets two ways of covering a bar against each other. It does not rate either against a type test: no partial-discharge, impulse or power-frequency withstand result for a taped bar or a sleeved one appears in these sources, and ANSI C37.20.2 is cited by the manufacturer as the standard the parts meet for switchgear application — not as a result for a particular panel. Nor does it say what the bar underneath is allowed to run at; that is a busbar sizing question, not a covering one.

Send the bar section and the assembly state

A size band comes back in one reply from four figures: bar width and breadth in millimetres, run length, system voltage, and whether the joint can be dismantled. The last of those decides tape or sleeve.